Voltage drop calculator

Estimate voltage drop in DC, single-phase or balanced three-phase wiring from cable size or resistance.

Get started

  1. Choose a model. For three phase, enter line-to-line voltage and line current. Enter one-way distance once.
  2. The distance limit uses your chosen drop percentage. Check ampacity, temperature and installation requirements separately.

Example

Input

120 V, single phase, 500 ft, 1 A and 1.2 Ω/km

Expected result

0.37 V drop, 0.30%

Try it

Good to know

The calculation runs in your browser. Use consistent units in fields with no explicit unit.

Calculation method

Use one-way length and identical parallel conductors. Multiply I·L·R by 2 for DC or single phase and √3 for balanced three phase. For lagging AC, R and X contribute through the power factor. Wire-size estimates use nominal resistance near 20 °C; use manufacturer data for the actual cable.

ΔV=kILReffn,k=2 (DC, 1)ϕ,k=3 (3)ϕ\Delta V=\frac{k I L R_{\rm eff}}{n},\quad k=2\ \text{(DC, 1)}\phi,\quad k=\sqrt{3}\ \text{(3)}\phi
Reff=Rcos⁡θ+Xsin⁡θ,%ΔV=100ΔVVsR_{\rm eff}=R\cos\theta+X\sin\theta,\quad \%\Delta V=100\frac{\Delta V}{V_s}

Calculation mode

Known resistance or impedance
  • Resistance or impedance per length
  • Unit per length · Ω/km / Ω/m / mΩ/m / Ω/1000 ft / Ω/ft / mΩ/ft
  • Voltage · V
  • Circuit · DC / Single-phase AC / Three-phase AC
  • Conductors per phase
  • One-way distance
  • Length unit · ft / m / mi / km
  • Current · A
  • Drop limit for distance estimate · %
Estimate from wire gauge
  • Material · Copper / Aluminum / Silver / Gold
  • Wire size
  • Voltage · V
  • Circuit · DC / Single-phase AC / Three-phase AC
  • Conductors per phase
  • One-way distance
  • Length unit · ft / m / mi / km
  • Current · A
  • Drop limit for distance estimate · %
Estimate from area
  • Material · Copper / Aluminum / Silver / Gold
  • Cross-sectional area · mm²
  • Voltage · V
  • Circuit · DC / Single-phase AC / Three-phase AC
  • Conductors per phase
  • One-way distance
  • Length unit · ft / m / mi / km
  • Current · A
  • Drop limit for distance estimate · %
Resistance and reactance
  • Resistance
  • Reactance per length
  • Unit per length · Ω/km / Ω/m / mΩ/m / Ω/1000 ft / Ω/ft / mΩ/ft
  • Lagging power factor
  • Voltage · V
  • Circuit · DC / Single-phase AC / Three-phase AC
  • Conductors per phase
  • One-way distance
  • Length unit · ft / m / mi / km
  • Current · A
  • Drop limit for distance estimate · %